IEC 60335-2-40: Flammable Refrigerant Test Items
IEC 60335-2-40 is the safety standard for air conditioners, heat pumps and dehumidifiers. Korea's KC 60335-2-40 (KATS Notice 2022-0105) is based on the 2018 edition (Ed. 6) of IEC 60335-2-40; the current IEC edition is the 2024 edition (Ed. 8).
Charge limits (Annex GG)
Charge limits are set in bands (m1, m2, m3) obtained by multiplying the refrigerant's LFL (kg/m³) by fixed volumes, which determine the allowed charge and installation space. Under KC 60335-2-40, A3 refrigerants use 4, 26 and 130 m³, and A2L refrigerants use 6, 52 and 260 m³, multiplied by the LFL.
Korean deviation
KC 60335-2-40 adds outdoor-unit rooms (실외기실) to Table GG.1 of Annex GG.
How AL solutions' test items map
- Charge review — maximum charge and minimum installation area for the refrigerant and room size
- Leak test and concentration measurement — reproduce a leak and compare the surrounding concentration with the LFL
- Ignition source assessment — location and temperature of arcing parts and hot surfaces
- Safety measures — leak detection, circulation/ventilation fans and shut-off devices
- Refrigerant circuit tightness — joints, pressure and tightness tests
- Markings and manuals — flammable refrigerant warnings and installation/service instructions